Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM06187
Parcel: 12419040H

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM06187
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2020 MARTIN BROWN FIRE REVIEW Approved
04/23/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. The wall sections show R-19 batt insulation in the exterior walls but COMcheck calls out R-20 batt insulation. [Initial comment: Coordinate the wall insulation shown in the building section (A3.2) with the wall insulation shown in the wall sections on sheet D1 and the COMcheck envelope assemblies. Reference: Section 107.2.1, IBC 2018.]
2. Comment not resolved. Where is the long-vent dryer specified? Mechanical General Note #13 on sheet M1.1calls for a maximum equivalent dryer vent length of 35-feet. [Initial comment: The equivalent length of the dryer duct appears to be in excess of 35-feet. Provide the dryer manufacturer's installation instructions that support the proposed duct design. Reference: Section 504.8.4, IMC 2018.]
05/01/2020 LOREN MAKUS ENGINEERING REVIEW Approved
05/13/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/14/2020 STEVE SHIELDS ZONING REVIEW Approved
05/28/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved