Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM06176
Parcel: 106121460

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T19CM06176
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide Minimum 100 amp pedestals for the units per NEC 550.32b. Indicate this on the line diagram.
2. Provide a grounding detail for the pedestals. NEC 250
3. Provide a manufacturer cut sheet for the pedistals.
Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements.