Permit Number: T19CM06154
Parcel: 114111150

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM06154
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide more electrical detail showing Conduit, conductor sizes and types feeding the new control building. Where the feeders originate and how they terminate at the control building. Include a grounding detail for the building.
2. It is unclear as to how or what the equipment is terminated to in the control building or control cabinet. Perhaps provide a complete line diagram showing feeders or equipment branch circuits from source terminations to loads, identify all cabinets and or panels.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
10/04/2019 IMONSHI1 ZONING REVIEW Reqs Change Zoning cannot approve until archealogical review on this site has been approved.

Please contact Allison Diehl at Allison.Diehl@tucsonaz.gov asking for questions and review of plans
10/07/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 6; Building Section Key Notes: Note 7 has a Detail B indicated at the end of the note. Please add to the Note that Detail B is an alternate for the steel angles lintel.
2. Sheet 6; Building Section Key Notes: The thickened slab at the edge of the pad (Note 6) indicates a Key Note 12 at that location. Only one-#4 is indicated at the top and at the bottom. Please revise.
3. Sheet 6; Building Section Key Notes: Note 13 indicates wall reinforcing shall extend 16" or 14" beyond the opening. The Right Elevation indicates 16" or 24". Please verify.
4. General: Please provide structural calculations for this project.
5. General: Please provide a Special Inspection Certificate with Parts A and B completed.
6. General: Please provide written responses to all review comments.
10/07/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/07/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/07/2019 ROBERT SHERRY WATER REVIEW Passed
10/11/2019 MASHFOR1 FIRE REVIEW Approved
10/22/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2019 SBORZAK1 REJECT SHELF Completed