Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM06092
Parcel: 12613018B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM06092
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2019 ALEXANDRA HINES ZONING REVIEW Approved Lot combo put in records.
09/19/2019 MARTIN BROWN FIRE REVIEW Approved
09/19/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved