Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T19CM06081
Parcel: 140418480

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM06081
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2019 PAUL CAMARENA ZONING REVIEW Approved
10/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/17/2019 ROBERT SHERRY WATER REVIEW Completed
10/17/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
10/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section 2902.1, IBC 2018 requires two drinking fountains and a service sink in addition to the fixtures you have provided. [Initial comment: Calculate the number of required plumbing fixtures required for the suite. Include the occupants of both the office and the warehouse. Reference: Section 2902.1, IBC 2018.]
2. The specified thermostatic mixing valve is listed to ASSE 1070, not ASSE 1017 as shown on the mixing valve schedule. [Initial comment: Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.]
3. The plumbing drawings still show vents running horizontally prior to rising 6" above the flood rim of the fixture. [Initial comment: Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally (e.g. vents for water closets and the floor sink. Reference: Section 905.4, IPC 2018.]