Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM06072
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. 2. The plumbing fixture schedule calls out two new hand sinks but only one new hand sink is shown - is there a second sink? |
| 09/03/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the physical configuration of the Type I hood and grease duct specified on the mechanical kitchen hood schedule with the hood detail shown on sheet A3. 2. Verify the construction of the wall behind and on each end of the hood with respect to installation of a smooth, non-absorbent, non-combustible material over the gypsum or cementitious board. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/05/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 09/05/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/05/2019 | QJONES1 | REJECT SHELF | Completed |