Permit Number: T19CM05998
Parcel: 14041059A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05998
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/05/2019 ROBERT SHERRY WATER REVIEW Completed
09/05/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/05/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The basis of the structural calculations for the support of the mechanical equipment is a single unit weighing 200-pounds, located on the roof. Revise the structural calculations using the actual unit weights (302-pounds for the indoor unit and 435-pounds for the outdoor unit).
2. Provide ventilation for the Audio-visual room per Table 403.3.1.1, IMC 2018.
3. Provide an energy analysis of the installation of twelve Solatubes (e.g. COMcheck envelope alteration). Reference: Sections C503.1 and C503.3.3, IECC 2018.
09/16/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet EP102. Verify or provide a weather proof GFI protected receptacle on the roof for AC maintenance. NEC 210.63.
2. Provide complete compliance with the 2018 IECC for the lighting.
Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2019 QJONES1 APPROVAL SHELF Completed
09/18/2019 QJONES1 OUT TO CUSTOMER Completed
09/18/2019 QJONES1 REJECT SHELF Completed