Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T19CM05974
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2019 | SAMUEL ROGERS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: Samuel Rogers Planner PROJECT: T19CM05974 2301 E 7th St. Add garage and bedroom suite TRANSMITTAL: 8/20/2019 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. The north side minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The proposed setback is 1 foot. The west side minimum setback to a side street property line is ten (10) feet (UDC Section 6.4.5.C.1.b), the proposed setback is 1 foot. DDO is required. |
| 08/20/2019 | SROGERS2 | ENGINEERING | REVIEW | Passed | |
| 08/20/2019 | SROGERS2 | NPPO | REVIEW | Passed | |
| 10/23/2019 | ARUIZ1 | BUILDING-RESIDENTIAL | REVIEW | Needs Review |