Permit Number: T19CM05973
Parcel: 111081860

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T19CM05973
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2019 DAVID RIVERA ZONING REVIEW Reqs Change TO: Development Services Department
Plans Coordination Office

FROM: Iman Monshizadeh
PDSD Zoning Review Section

PROJECT: La Promesa Apartments - New Parking Area Carports
Development Package (1st Review) 2485 N Alvernon Way
T19CM05973 - O-3 Zoning

TRANSMITTAL DATE: September 4th, 2019
DUE DATE: September 18th, 2019


1. Zoning has revied the building plans for the carport structures, cannot approve at this time until DP is approved
09/12/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet SP-2DP; Plan: The roof overhangs for the carports are required to be setback a minimum of 2'-6" from property lines and 5'-0" from other roof overhangs. Please verify on the plan those requirements are met.
2. Sheet SP-2DP; Plan: The face of the carport columns are required to be setback a minimum of 5'-0" from property lines and 10'-0" from other carport columns. Please verify on the plan those requirements are met.
3. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
09/25/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change once the development package has been approved, engineering will review and approve the building plans

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2019 AMARTIN1 OUT TO CUSTOMER Completed