Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM05973
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2019 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | TO: Development Services Department Plans Coordination Office FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: La Promesa Apartments - New Parking Area Carports Development Package (1st Review) 2485 N Alvernon Way T19CM05973 - O-3 Zoning TRANSMITTAL DATE: September 4th, 2019 DUE DATE: September 18th, 2019 1. Zoning has revied the building plans for the carport structures, cannot approve at this time until DP is approved |
| 09/12/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet SP-2DP; Plan: The roof overhangs for the carports are required to be setback a minimum of 2'-6" from property lines and 5'-0" from other roof overhangs. Please verify on the plan those requirements are met. 2. Sheet SP-2DP; Plan: The face of the carport columns are required to be setback a minimum of 5'-0" from property lines and 10'-0" from other carport columns. Please verify on the plan those requirements are met. 3. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 09/25/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | once the development package has been approved, engineering will review and approve the building plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/26/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |