Permit Number: T19CM05967
Parcel: 125043160

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T19CM05967
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2020 SARAH MEGGISON ZONING REVIEW Reqs Change FROM: Sarah Meggison, AICP
Planner

PROJECT:
T19CM05967
2216 E Hawthorne St
Garage/Bedroom Addition

TRANSMITTAL: August 20, 2019
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant proposes to construct a garage with a bedroom above in the rear of the property with the following proposed setbacks:

- West Elevation required setback is 14.29-feet based on a 21.66-foot wall height and the applicant proposes an 11-foot setback.
- South Elevation required setback is 12-feet based on 18-foot wall height and the applicant proposes a 6-foot setback.

A DDO is required prior to zoning approval.
01/29/2020 SMEGGIS1 NPPO REVIEW Passed
02/10/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Needs Review
08/20/2019 SMEGGIS1 ENGINEERING REVIEW Passed