Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2019 PAUL CAMARENA ZONING REVIEW Approved
08/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/19/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2019 LOREN MAKUS ENGINEERING REVIEW Passed
08/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS1; Code Review: Please clarify the area designations for the occupant load calculations. The plan (Sheet A1.0) does not specifically identify the clubhouse or waiting areas.
2. Sheet A1.0; Floor Plan: Please provide on the Code Review (Sheet TS1) the calculations for the required plumbing fixtures. The plan indicates one restroom for 70 occupants.
3. Sheet A1.0; Floor Plan: Please indicate on this plan the exiting for this building.
4. General: Please provide written responses to all review comments.
08/19/2019 ROBERT SHERRY WATER REVIEW Completed
08/19/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide calculations for the required number of plumbing fixtures.
2. Provide a plumbing design for the revisions to the breakroom.
08/19/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/20/2019 MARTIN BROWN FIRE REVIEW Approved