Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05929
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2019 | PAUL CAMARENA | ZONING | REVIEW | Approved | |
08/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/19/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
08/19/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet TS1; Code Review: Please clarify the area designations for the occupant load calculations. The plan (Sheet A1.0) does not specifically identify the clubhouse or waiting areas. 2. Sheet A1.0; Floor Plan: Please provide on the Code Review (Sheet TS1) the calculations for the required plumbing fixtures. The plan indicates one restroom for 70 occupants. 3. Sheet A1.0; Floor Plan: Please indicate on this plan the exiting for this building. 4. General: Please provide written responses to all review comments. |
08/19/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/19/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations for the required number of plumbing fixtures. 2. Provide a plumbing design for the revisions to the breakroom. |
08/19/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/20/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |