| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the distance from the hot water source to the hot water connection of the lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 11/18/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved |