Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T19CM05881
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05881
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Common Area
1. Sheet G-1; Code Check: The Code Check indicates 23 occupants, while the Plumbing Calculations indicates 73 occupants. Please coordinate.
2. Sheet G-1; Plumbing Calculations: This table references the 2012 IBC. Please revise.
3. Sheet A-1; Architectural Floor Plan: None of the public restrooms shown are accessible. Please indicate on the drawings the location of the accessible public restrooms, and verify the requirement of the IBC Section 2902.3.3 is met for travel distance.
4. Sheet A-2; Reflected Ceiling Plan: At the north portion of this space, two exit signs (Keyed Note 5) are indicated, while the electrical Sheet E1 indicates one exit sign. Please verify.
5. General: Please provide written responses to all review comments.

Verifone
1. Sheet G-1; Key Map: The Project Location indicates the fourth floor. Please revise.
2. General: The combination of the Common Area portion of this permit and the Verifone portion of this permit could create confusion concerning cost and construction. If different general contractors are selected (one for the Common Area controlled by the building owner and one for the Verifone area controlled by the tenant), separating the cost of each area along with the construction timing could be a challenge. Please verify.
3. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
09/16/2019 ROBERT SHERRY WATER REVIEW Completed
09/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. This plumbing review is for alterations to the common area only.
2. Show the location of the two drinking fountains noted in the plumbing calculations on sheet G-1. (Note, the 2018 IBC is the current code.) Reference: Section 107.2.1, IBC 2018.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Sections C404.5 and C503.5, IECC 2018.
09/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed This review is for alterations to the common area only.
09/24/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. The electrical line diagram shows the new panels rated at 225 amps, and the panel schedules show 200 amps. Please clarify.
Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal requirements. 2012 Tucson/Pima County Outdoor Lighting Code