Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05845
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2019 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
08/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | AHINES2 | ENGINEERING | REVIEW | Passed | |
08/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A023-PH4; Plan 7: Per the 2009 ICC/ANSI A117.1 Figure 604.5.1, a vertical grab bar is required. Please indicate and dimension the grab bar on Side Elevations B and C. 2. Sheet A051-PH4; Plumbing Fixtures: The lavatories indicate 5.2875, which is rounded down to 5. This should be rounded up to 6 per the IBC Section 2902.1.1. Please revise. 3. Sheet A201-PH4; Construction Plan: Please indicate the construction of the new wall (stud size/gauge/spacing). 4. General: Please provide written responses to all review comments. |
08/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
08/15/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |