Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05842
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the HW supply to the lavatory, P1A, so the distance to the hot water source complies with Section C404.5, IECC 2018. 2. Limit the water flow to the lavatory, P1A, to no more than 0.25 gallons per cycle. 3. Provide insulation for the hot water recirculation loop. |
08/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/16/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
08/16/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/16/2019 | NROSS1 | ENGINEERING | REVIEW | Passed |