Permit Number: T19CM05842
Parcel: 117130410

Address:
20 E OCHOA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05842
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/15/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/15/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2019 ROBERT SHERRY WATER REVIEW Completed
08/15/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/15/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the HW supply to the lavatory, P1A, so the distance to the hot water source complies with Section C404.5, IECC 2018.
2. Limit the water flow to the lavatory, P1A, to no more than 0.25 gallons per cycle.
3. Provide insulation for the hot water recirculation loop.
08/16/2019 NROSS1 ENGINEERING REVIEW Passed
08/16/2019 NICHOLAS ROSS ZONING REVIEW Approved
08/16/2019 MARTIN BROWN FIRE REVIEW Approved