Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05842
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
08/15/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/15/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the HW supply to the lavatory, P1A, so the distance to the hot water source complies with Section C404.5, IECC 2018. 2. Limit the water flow to the lavatory, P1A, to no more than 0.25 gallons per cycle. 3. Provide insulation for the hot water recirculation loop. |
08/16/2019 | NROSS1 | ENGINEERING | REVIEW | Passed | |
08/16/2019 | NICHOLAS ROSS | ZONING | REVIEW | Approved | |
08/16/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |