Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM05817
Parcel: 13319166A

Address:
850 N MANN AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T19CM05817
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2019 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T19CM05817 (Project Number)
Residential Building Plan Review (Project Type) (1st Review)
850 N MANN AV - R1 Zoning

TRANSMITTAL DATE: August 21, 2019

DUE DATE: August 29, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. Comment: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.

02. COMMENT: Provide a line site drawing or remove the aerial from the site drawing.


03. COMMENT: Per the proposed Garage addition it appears that on the north property line there is a structure that is encroaching into the property.


04. COMMENT: Please provide an approved lot line realignment that includes the appropriate setback for the entire structure. Clarify if a land split/ lot reconfiguration was processed and approved by PDSD and the documents recorded by Pima County?


05. COMMENT: Was a survey done to verify the new lot line location, if so submit a copy with the next submittal.


If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 791-5550 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
08/29/2019 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T19CM05817
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Limit all code references to those recognized by the City of Tucson. Update the 2006 IRC code reference at note #4 sheet A3.

FLOOR PLANS:

1. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, R302.5.1.
2. Show a ½" gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R302.6.

STRUCTURAL PLANS:

1. Provide roof joist size/series for determining performance compliance, R301.1

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.
If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/13/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed