Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05813
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2019 | MALLORY RESS | ZONING | REVIEW | Approved | |
| 08/14/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/14/2019 | RMCCOY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/14/2019 | MRESS1 | ENGINEERING | REVIEW | Passed | |
| 08/14/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1.0; Exiting: The Code Review indicates 2 exits for this project. Per the IBC Section 1016.2, an exit through a storage room is not allowed. Please revise the Code Review note, and verify the travel distance requirements indicated in Table 1006.2.1 are met. 2. Sheet A1.0; Wall Legend: Wall Type 1 was not located on the plan. Please verify. 3. Sheet A2.0; Detail 2: This detail is for a 1-hour fire resistant rated wall. Where is this wall located? Please verify. 4. General: Please provide written responses to all review comments. |
| 08/14/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/14/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/14/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/14/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |