Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM05747
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/05/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The new panels and transformer shown on the line diagram do not correlate with the panel schedules and the panels shown on the electrical floor plans. 2. The designated branch circuit numbers and panels do not correlate with the panel schedules. 3. Due to the nature of discrepancies on the electrical plans, additional comments may be generated at the subsequent review. Ref; 2017 NEC, 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
09/05/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Sheet P1 still shows an indirec receptor located under the cabinet. [Initial comment: Indirect waste receptors shall not be installed in concealed spaces. Provide ready access to the waste receptor. Reference: Section 802.4, IPC 2018.] |