Permit Number: T19CM05741
Parcel: 12105012G

Address:
5502 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05741
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/29/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the new entry door (door 106) complies with the requirements of Section C503.3.2, IECC 2012. (Alternatively, see Section 5.1.3, exception 8, ASHRAE 90.1-2016).
08/29/2019 ROBERT SHERRY WATER REVIEW Completed
09/12/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/23/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T19CM05741

1) A separate development package, showing only the site and grading work(Sheets C1-C4), needs to be submitted as a separate review
2) Once the development package has been reviewed and approved, Engineering can approve the building plans. Plans are to be submitted electronically. See following links
a. https://www.tucsonaz.gov/file-upload-pdsd
b. https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
09/23/2019 PMARTIN1 ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: 5502 E GRANT RD
Building Plans (1st Review) 5502 E GRANT RD
T19CM05741

TRANSMITTAL DATE: September 23, 2019


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.


02. COMMENT: Zoning cannot approve until Development Package is approved.


If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
09/26/2019 MASHFOR1 FIRE REVIEW Approved
10/03/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A00.20; Floor Plan: Area B on the plan indicates a total occupant load of 7, while the Area Identification Box indicates 1106 SF and 8 occupants (Exit Door 1.B1 indicates 8 occupants). Please coordinate.
2. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area B indicates 7 occupants, while the Area Identification Box on the plan indicates 8 occupants. Please coordinate.
3. Sheet A00.20; Floor Plan: Area D on the plan indicates a total occupant load of 14, while the Area Identification Box indicates 250 SF and 17 occupants (Exit Door 1.C2 indicates 14 occupants). Please coordinate.
4. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area D indicates 14 occupants, while the Area Identification Box on the plan indicates 17 occupants. Please coordinate.
5. Sheet A00.20; Floor Plan: Area A on the plan requires two exits, and the distance between those exits is indicated as 53'-0". Under that distance, a note indicates a required 1/3 separation. That requirement is valid if the building is sprinklered. If not sprinklered (per Sheet A00.00), that separation should be indicated as 1/2 the diagonal dimension of the Area A. Please verify.
6. Sheet A00.20; Floor Plan: Area C on the plan indicates a total occupant load of 14, while the Area Identification Box indicates 1763 SF and 12 occupants (Exit Door 1.C1 indicates 14 occupants). Please coordinate.
7. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area C indicates 14 occupants, while the Area Identification Box on the plan indicates 12 occupants. Please coordinate.
8. Sheet A00.20; Egress Calculations: Please indicate on this sheet the maximum exit access travel distance (for all exits) is less that the allowable distance listed in Table 1017.2.
9. Sheet A02.01; Sheet Notes: Note 03 references Detail 20/A00.40 for an accessible symbol. Please revise that reference.
10. Sheet A11.00; General Notes: Note H references Sheet A08.01 for the Equipment Schedule. Please revise that reference.
11. Sheet A12.10; General Notes: Note D references Sheet A12.10 for all door head and jamb details. Please revise that reference.
12. General: Please provide written responses to all review comments.