Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05741
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/29/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that the new entry door (door 106) complies with the requirements of Section C503.3.2, IECC 2012. (Alternatively, see Section 5.1.3, exception 8, ASHRAE 90.1-2016). |
| 08/29/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/12/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/23/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T19CM05741 1) A separate development package, showing only the site and grading work(Sheets C1-C4), needs to be submitted as a separate review 2) Once the development package has been reviewed and approved, Engineering can approve the building plans. Plans are to be submitted electronically. See following links a. https://www.tucsonaz.gov/file-upload-pdsd b. https://www.tucsonaz.gov/files/pdsd/forms/Development_Package_and_Land_Division-Subdivision_Application.pdf John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
| 09/23/2019 | PMARTIN1 | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: 5502 E GRANT RD Building Plans (1st Review) 5502 E GRANT RD T19CM05741 TRANSMITTAL DATE: September 23, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments. 02. COMMENT: Zoning cannot approve until Development Package is approved. If you have any questions about this transmittal, Contact Paul Camarena any time during the week at (520) 837-4082 or by email Paul.Camarena@Tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 09/26/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 10/03/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A00.20; Floor Plan: Area B on the plan indicates a total occupant load of 7, while the Area Identification Box indicates 1106 SF and 8 occupants (Exit Door 1.B1 indicates 8 occupants). Please coordinate. 2. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area B indicates 7 occupants, while the Area Identification Box on the plan indicates 8 occupants. Please coordinate. 3. Sheet A00.20; Floor Plan: Area D on the plan indicates a total occupant load of 14, while the Area Identification Box indicates 250 SF and 17 occupants (Exit Door 1.C2 indicates 14 occupants). Please coordinate. 4. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area D indicates 14 occupants, while the Area Identification Box on the plan indicates 17 occupants. Please coordinate. 5. Sheet A00.20; Floor Plan: Area A on the plan requires two exits, and the distance between those exits is indicated as 53'-0". Under that distance, a note indicates a required 1/3 separation. That requirement is valid if the building is sprinklered. If not sprinklered (per Sheet A00.00), that separation should be indicated as 1/2 the diagonal dimension of the Area A. Please verify. 6. Sheet A00.20; Floor Plan: Area C on the plan indicates a total occupant load of 14, while the Area Identification Box indicates 1763 SF and 12 occupants (Exit Door 1.C1 indicates 14 occupants). Please coordinate. 7. Sheet A00.20 (Floor Plan); Egress Calculations: The Egress Calculation for Area C indicates 14 occupants, while the Area Identification Box on the plan indicates 12 occupants. Please coordinate. 8. Sheet A00.20; Egress Calculations: Please indicate on this sheet the maximum exit access travel distance (for all exits) is less that the allowable distance listed in Table 1017.2. 9. Sheet A02.01; Sheet Notes: Note 03 references Detail 20/A00.40 for an accessible symbol. Please revise that reference. 10. Sheet A11.00; General Notes: Note H references Sheet A08.01 for the Equipment Schedule. Please revise that reference. 11. Sheet A12.10; General Notes: Note D references Sheet A12.10 for all door head and jamb details. Please revise that reference. 12. General: Please provide written responses to all review comments. |