Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM05741
Parcel: 12105012G

Address:
5502 E GRANT RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T19CM05741
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2019 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: B of A ADA Upgrades
T19CM05741
Building Plan (Ok to Submit)

TRANSMITTAL DATE: August 12, 2019

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The striped area between the two (2) northern vehicle parking spaces is required to be a sidewalk meeting TSM Section 7-01.4.3 and physically separated from the vehicle parking area, see TSM Section 7-01.4.2

3. Demonstrate how the requirements of ICC A117.1-2009 Section 505.10 are met at the bottom of the proposed ramp/landing.

4. It does not appear that the site is meeting the requirements of 2018 IBC Chapter 11 Table 1106.1, 59 vehicle parking spaces provide requires 3 accessible vehicle parking spaces.

5. Until the building plan is approved by all other review agencies Zoning cannot approve the plan.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/12/2019 SSHIELD1 ADA REVIEW Passed See Zoning comments
08/13/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/15/2019 LOREN MAKUS ENGINEERING REVIEW Needs Review Site improvements include areas in FEMA Special Flood Hazard Area AH. A Floodplain Use Permit will be required.
08/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
08/19/2019 ENEWCOM1 FIRE REVIEW Needs Review