Permit Number: T19CM05740
Parcel: 13609019D

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T19CM05740
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2019 DAVID RIVERA ZONING REVIEW Approved
08/28/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
08/28/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/28/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/28/2019 ROBERT SHERRY WATER REVIEW Passed
09/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide more electrical detail showing Conduit, conductor sizes and types feeding the new control building. Where the feeders originate and how they terminate at the control building. Include a grounding detail for the building.
2. It is unclear as to how or what the equipment is terminated to in the control building or control cabinet. Perhaps provide a complete line diagram showing feeders or equipment branch circuits from source terminations to loads, identify all cabinets and or panels.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
09/13/2019 JOHN VAN WINKLE ENGINEERING REVIEW Passed
09/18/2019 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2019 SBORZAK1 OUT TO CUSTOMER Completed