Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM05740
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2019 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/28/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/28/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/28/2019 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 09/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide more electrical detail showing Conduit, conductor sizes and types feeding the new control building. Where the feeders originate and how they terminate at the control building. Include a grounding detail for the building. 2. It is unclear as to how or what the equipment is terminated to in the control building or control cabinet. Perhaps provide a complete line diagram showing feeders or equipment branch circuits from source terminations to loads, identify all cabinets and or panels. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
| 09/13/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 09/18/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2019 | SBORZAK1 | OUT TO CUSTOMER | Completed |