Permit Number: T19CM05656
Parcel: 12406132A

Address:
1050 E 8TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05656
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Floor Plan: A note on this plan indicates rated walls between the existing bedrooms are not required. In addition, the new partition Detail P1 indicates no rating on the new partition walls. Please indicate the code section on this sheet that allows walls between sleeping units to be unrated in an R-2 Occupancy Classification.
2. Sheet A2; Code Review: Note 6 indicates a sprinkler is not required because of existing use. Please indicate the code section on this sheet that allows an R-2 Occupancy Classification to be non-sprinklered.
3. General: The latest set of drawings (3-9-22 submittal) does not include all 6 updated sheets (S1, S2, A1, A2, M-101, and E-101). Please provide that set.
4. General: The emergency escape windows in the new Bedroom 3 will be allowed per the IEBC Section 505.3.
5. General: Please provide written responses to all review comments.
03/16/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed