Permit Number: T19CM05656
Parcel: 12406132A

Address:
1050 E 8TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM05656
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2022 STEVE SHIELDS ZONING REVIEW Approved
01/05/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/06/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Comment not addressed. No ventilation calculations are shown, and nothing shows how mechanical ventilation will be provided [Second comment: Comment not addressed. No ventilation calculations are shown, and nothing shows how mechanical ventilation will be provided.] [Initial comment: Provide calculations to verify that adequate mechanical ventilation will be provided for the occupied spaces due to the addition of a bedroom. Reference: Section 403.3.1.1, IMC 2018.]
01/19/2022 SBLOOD1 ENGINEERING REVIEW Approved
12/29/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Floor Plan: Emergency escape and rescue openings are required per the IBC Section 1030 for sleeping units in Group R-2 occupancies. Please indicate on the Floor Plan that the windows in the new bedroom meet the requirements of the IBC Sections 1030.1.1, 1030.2, and 1030.3.