Review Details: RESUBMITTAL - TI ALL
Permit Number - T19CM05656
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 01/05/2022 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/06/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. No ventilation calculations are shown, and nothing shows how mechanical ventilation will be provided [Second comment: Comment not addressed. No ventilation calculations are shown, and nothing shows how mechanical ventilation will be provided.] [Initial comment: Provide calculations to verify that adequate mechanical ventilation will be provided for the occupied spaces due to the addition of a bedroom. Reference: Section 403.3.1.1, IMC 2018.] |
| 01/19/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
| 12/29/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Floor Plan: Emergency escape and rescue openings are required per the IBC Section 1030 for sleeping units in Group R-2 occupancies. Please indicate on the Floor Plan that the windows in the new bedroom meet the requirements of the IBC Sections 1030.1.1, 1030.2, and 1030.3. |