Permit Number: T19CM05656
Parcel: 12406132A

Address:
1050 E 8TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05656
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

10. You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.
03/16/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Could not locate electrical plans.
03/17/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to verify that adequate mechanical ventilation will be provided for the occupied spaces due to the addition of a bedroom. Reference: Section 403.3.1.1, IMC 2018.
03/17/2021 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Building Comments:
1. New Floor Plan: The new interior partitions do not indicate a fire resistance rating as required by the IBC Section 420.2. Please revise and indicate a U.L. Listing Number for that fire resistance rating.
2. Site Plan: The existing building indicates a 3.5 story building of 69,148 SF. Should this be revised to a three story building? Please verify and revise.
3. Site Plan: This sheet indicates the Occupancy Classification as R-3. Per the IBC Section 310.3, should this apartment building be classified as R-2? Please verify.
4. Site Plan: Please indicate on this drawing if the building has an automatic sprinkler system.
5. General: Please provide a project valuation (labor + materials).
6. General: Please provide written responses to all review comments.
03/17/2021 ROBERT SHERRY WATER REVIEW Completed
03/17/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/19/2021 ELISA HAMBLIN ZONING REVIEW Reqs Change T19CM05656
1050 E 8th St
Building plans

1. The development package for this project has not yet been approved. DP19-0261 must be approved prior to building plan approval. Outstanding comments can be viewed online here: https://www.tucsonaz.gov/pro/pdsd/review/detail/12406132A/DP19-0261/331545/
2. Once the DP is approved, the building plans will be reviewed for consistency.
3. Zoning will not provide approval on the building plans untial all commercial plan reivewers comments have been addressed.
Elisa Hamblin, AICP
elisa.hamblin@tucsonaz.gov
03/25/2021 JPEELDA1 FIRE REVIEW Approved APPROVED BY JVINCENT 2/22/2021