Permit Number: T19CM05585
Parcel: 132191160

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T19CM05585
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/19/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The new HVAC load calculations still indicate a scheduled cooling capacity (221.8 MBH for RTU-1, RTU-2, FC-1, and MUA-1) that is nearly three times the total cooling load for the building (63.2 MBH). How is this justified? [Second comment: The HVAC heating/cooling load calculations show a total building cooling load of 60,199 BTUH but the design documents show a total cooling capacity of 148,800 BTUH if the cooling capacity of the make up air unit (73,000 BTUH) is not included. How is this justified?] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018.]
2. Include the structural details on a full-size drawing as part of the document set. [Second comment: The hood installation drawings show the hood supported from ceiling joists with all-thread and Unistrut. Provide structural calculations to show that the building structure is adequate to support the hood.] [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.]
3. Submit a document set that includes all of the current drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2019 SBORZAK1 REJECT SHELF Completed