Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T19CM05585
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The new HVAC load calculations still indicate a scheduled cooling capacity (221.8 MBH for RTU-1, RTU-2, FC-1, and MUA-1) that is nearly three times the total cooling load for the building (63.2 MBH). How is this justified? [Second comment: The HVAC heating/cooling load calculations show a total building cooling load of 60,199 BTUH but the design documents show a total cooling capacity of 148,800 BTUH if the cooling capacity of the make up air unit (73,000 BTUH) is not included. How is this justified?] [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018.] 2. Include the structural details on a full-size drawing as part of the document set. [Second comment: The hood installation drawings show the hood supported from ceiling joists with all-thread and Unistrut. Provide structural calculations to show that the building structure is adequate to support the hood.] [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.] 3. Submit a document set that includes all of the current drawings. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/02/2019 | SBORZAK1 | REJECT SHELF | Completed |