Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05585
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/17/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G000; Building Code Summary: Please indicate on this sheet the Occupancy Classification is A-2 (restaurant), but shall be classified as a Group B Occupancy per the IBC Section 303.1.2(1). 2. Sheet G000; Building Code Summary: The MAXIMUM AREA/STORY/HEIGHT references the IBC Section 503 (2012 IBC). Please revise those references to Table 504.3 (Allowable Building Height in Feet Above Grade Plane), Table 504.4 (Allowable Number of Building Stories Above Grade Plane), and Table 506.2 (Allowable Building Area). These are from the 2018 IBC. 3. Sheet G000; Building Code Summary: The MAXIMUM AREA/STORY/HEIGHT indicates 12,500/2/55 (2012 IBC). Please revise these to 36,000 SF (Table 506.2), 3 Stories (Table 504.4), and 60' (Table 504.3) per the 2018 IBC. Verify. 4. Sheet G000; Building Code Summary: The Occupant Load references Table 1004.1.1 (2012 IBC). Please revise that reference to Table 1004.5 (2018 IBC). Verify. 5. Sheet G002; Detail 19 (Side Wall Grab Bar at Water Closets): Please add the vertical grab bar per the 2009 ICC/ANSI Figure 604.5.1. 6. Sheet A200; Elevations: Please add a note on this sheet to reference Sheet A102 for the Equipment Schedule Callouts. 7. Sheet A400; Section 7: Please indicate the wall stud size and gauge (as required) on this section. 8. Sheet A400; Section 7: Please extend this section to include the connection of the stud wall to the existing structure above, and the connection of the threaded rod to the existing structure above. 9. Sheet A400; Detail 3: Please add an enlarged detail indicating the connection of the window awning to the existing wall. 10. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
09/17/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
09/18/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The International Fuel Gas Code, 2018, is the controlling code for this activity, not the 2012 International fuel gas Code as shown on sheet P100. Reference: Section 101.2, IPC 2018. 2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 4. Interior waste piping upstream of the grease interceptor shall have a minimum slope of ΒΌ" per foot (2% slope). Reference: Section 704.1, IPC 2018. 5. Verify that each compartment of the 3-compartment sink has a separate indirect waste pipe to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018. 6. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. 7. Provide a design for the venting system and the venting materials to be used for the proposed water heater. Reference: Section 503.1, IFGC 2018. |
09/18/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/19/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/19/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The 2018 International Energy Conservation Code with Local Amendments is the relevant energy code for this project (see economizer specification on sheet M400). 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Sections C403.1.1 and C502.2.3, IECC 2018. 3. Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018. 4. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018. 5. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2018. 6. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018. 7. Show that the hood installation complies with Section 507.2.6, IMC 2018 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood (note that wood studs covered by gypsum board and a sheet of stainless steel are considered combustible construction by the IMC). |