Permit Number: T19CM05544
Parcel: 109224470

Address:
5650 E RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05544
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the enlarged waste and vent plan on sheet P3.1 with the waste and vent riser diagram on sheet P3.2.
2. The 3" vent up from the first floor may not be reduced in size as it heads to the 3" VTR. It is shown as reducing to a 2" vent on both P3.1 and P3.2.
3. See the mark-ups on sheets P3.1 and P3.2 in 4-4th City Submittal.