Permit Review Detail
Review Status: Completed
Review Details: RESUB - SITE/GRADING ALL
Permit Number - T19CM05544
Review Name: RESUB - SITE/GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2019 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T19CM05544 -Storage use group/ personal storage use Building Plan (2nd Review) Related to DP19-0058 5650 E RIVER RD - Zoning PAD 22 TRANSMITTAL DATE: November 21, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has done a review of the building plans. In addition, while the building are consistent as it relates to the zoning review purview (as noted above) zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans 02. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the approved DP. If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the Commercial Plans reviewers approve the building plans zoning can approve the plans. 02. COMMENT: Remove all clouds and deltas from the plan If you have any questions about this transmittal, Contact Paul Camarena at (520) 837-4082 or by email Paul.Camarena@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 12/09/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved: specifying that the programmable thermostats have the capability, "as required for operation of heating and cooling controls" is not adequate. [Initial comment: Show that each HVAC unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.4.2 through C403.4.2.3, IECC 2018.] |
| 12/09/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. See Table C404.5, IECC 2018 which limits the maximum distance from a public lavatory to the hot water source to 2-feet for a ½" pipe, not 50-feet. [Initial comment: Show how the distance from the hot water source to the hot water termination for the first floor public lavatories complies with the requirements of Section C404.5, IECC 2018.] 2. Plumbing fixtures located above the rim elevation of the next upstream manhole (2482.29') may not discharge through the backwater valve. [Initial comment: According to the civil drawings, the FFE is 2483.00' and a backwater valve is required. Show the location of the backwater valve and verify that no fixtures located above the rim elevation of the next upstream manhole (2482.29') discharge through the backwater valve. Reference: Section 714.1, IPC 2018 as amended by the City of Tucson.] |
| 12/17/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 1; General: In Part B of the Special Inspection Certificate form, the name of the person providing each special inspection for each category was not listed. Please provide. 2. Previous Comment 7; Sheet T1.0; Code Analysis (Plumbing Fixture Calculation): Although the appeal to the Building Official allows three total restrooms (not including the apartment), the correct plumbing calculation should be indicated on this sheet. The B occupancy should indicate 12 male and 11 female occupants. The S-1 occupancy should indicate 121 male and 120 female occupants. Per the IBC Section 2902.1.1, the required water closets should be (12/25) + (121/100) = 0.48 + 1.21 = 1.69 for males (round up to two), and (11/25) + (120/100) = 1.64 for females (round up to two). This would total four water closets (not including the apartment). In addition, please add a note on Sheet T1.0 indicating an appeal to the Building Official was approved, allowing a total of three water closets (not including the apartment water closet). 3. Previous Comment 7; Sheet T1.0; Code Analysis (Plumbing Fixture Calculation): Although the appeal to the Building Official allows three total restrooms (not including the apartment), the correct plumbing calculation should be indicated on this sheet. The B occupancy should indicate 12 male and 11 female occupants. The S-1 occupancy should indicate 121 male and 120 female occupants. Per the IBC Section 2902.1.1, the required lavatories should be (12/40) + (121/100) = 0.30 + 1.21 = 1.51 for males (round up to two), and (11/40) + (120/100) = 0.28 + 1.20 = 1.48 for females (round up to two). This would total four lavatories (not including the apartment). In addition, please add a note on Sheet T1.0 indicating an appeal to the Building Official was approved, allowing a total of three lavatories (not including the apartment water closet). 4. Previous Comment 12; Sheet T1.1; Basement Plan: The path of travel to the toilet facilities was not found on the Basement Plan. Please verify. 5. Previous Comment 13; Sheet T1.2; First Floor Plan: The dead end corridor length at the restrooms was not found on the First Floor Plan. Please verify. 6. Sheet T1.3; Second Floor Plan: Please revise the extent of the rated wall at Stair 3 to include the south wall of the stair (common to the bathroom). 7. Previous Comment 20; Sheet A8.0; Detail 13: The hatch size was not revised to meet the requirements of the IBC Section 1011.12.2. Please revise. 8. General: Please provide written responses to all review comments. |
| 12/18/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E0.3, E1.0. The plans must provide the following information per the 2012 Tucson/Pima County Outdoor Lighting Code. (a) Indicate the parcel size in acres. Show total allowed lumens per acre and total proposed lumens per acre. (b) Indicate the lighting area and option used per Table 401.1 (c) Indicate lumen calcs for both Full Cut Off and Unshielded luminaires. (d) Indicate whether a special inspection is required or not, per section 104.2.2 and 106.2. (e) Provide compliance for lamp color temperature per section 402.1 (3500K) 2. Ref; Plan Sheet E4.0. The feeders for the elevator #1 are undersized for the OCPD in the electrical service equipment. Please clarify. Ref; 2018 IBC 107.2.1, 2018 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code (can be printed or downloaded from www.tucsonaz.gov/pdsd). |
| 12/20/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/23/2020 | SBORZAK1 | REJECT SHELF | Completed |