Permit Number: T19CM05444
Parcel: 12803008B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05444
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/16/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The grease schematic shows the three drains of the 3-compartment sink combining into one drain to the floor sink. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.]
2. The requirement is for the hot water source (i.e. the recirculating HW loop) to be within 2-feet of the lavatories. The lengths of the two HW drops appear to be longer than 2-feet. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]