Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM05444
Parcel: 12803008B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T19CM05444
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/12/2019 PAUL CAMARENA ZONING REVIEW Approved FROM: David Jellen
PDSD Zoning Review Section

PROJECT: Jersey Mikes
Building Plan (2nd Review) 5720 E BROADWAY BL
T19CM05444

TRANSMITTAL DATE: October 28, 2019

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments.


02. COMMENT: The parking calculations on the Building Plan and the Development Package do not match. The DP has a total of 27 parking spaces provided, while the Building Plan has a total of 29 parking spaces provided. Revise parking calculations on the next submittal.



If you have any questions about this transmittal, Contact David Jellen at (520) 837-4082 on Monday through Wednesday or by email at David.Jellen@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email at Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
11/13/2019 ROBERT SHERRY WATER REVIEW Completed
11/13/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. If PEX tubing is used for water distribution, provide a guide for the contractor convert the copper pipe sizes shown on the drawing to the appropriate size for PEX tubing. Reference: Section 303.2, IPC 2018.
2. If PEX tubing is used for water distribution, provide an approved method of disinfection that will not expose the PEX tubing to excessive levels of chlorine. Reference: Sections 303.2 and 610.1, IPC 2018.
3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.
4. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
5. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
11/13/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
2. Provide information to show that the termination of the restroom exhaust fans complies with the requirements of Section 501.3.1 (3), IMC 2018.
3. Show how the proposed termination of the Type I exhaust duct and exhaust fan complies with requirements of Sections 506.3.13.3 and 506.5.6, IMC 2018.