Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T19CM05433
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2019 | RMCCOY1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/02/2019 | RMCCOY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/08/2019 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Per section 1204.3.1 of the 2018 International Fire Code, a 4' perimeter is required on all sides. There is only 2' on the North side of the building. |
| 08/15/2019 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: 555 E RIVER ROAD ASSOCIATES LP Building Plan (1st Review) 555 E RIVER ROAD T19CM05433 - Parking Solar Canopy TRANSMITTAL DATE: August 15, 2019 DUE DATE: August 27, 2019 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 01. COMMENT: Zoning has reviewed the plan and cannot approve at this time. Please address the following comments. 02. COMMENT: Zoning cannot approve until Development Package is approved. If you have any questions about this transmittal, Contact Paul Camarena at (520) 791-5550 or by email Paul.Camarena@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
| 08/23/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Verify that the bus is marked "TAP" by the manufacturer at the point of the PV utility interconnection. Otherwise provide for a field evaluation to be performed by a qualified testing agency to re-certify the electrical equipment. 2. Per the inverter cut sheets, it appears inverter #2 (30KW) is not equipped with an integrated AC disconnect. Provide a detail with dimensions showing how the inverters are mounted. Also provide compliance with NEC 705.70 (2). Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
| 08/23/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/28/2019 | AMARTIN1 | OUT TO CUSTOMER | Completed |