Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05348
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2019 | SMEGGIS1 | ZONING | REVIEW | Approved | |
| 07/29/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation of EF-1 and EF-2 so that they exhaust the restrooms whenever HVAC air is supplied to the rooms during ocupied hours. |
| 07/29/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Coordinate exhaust fan controls with mechanical requirements. See mechanical review comments. 2. Revise the panel schedule to correlate with the water heater circuit numbers. 3. Provide for Tamper Resistant receptacles as required per NEC art 406.12. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |
| 07/29/2019 | SMEGGIS1 | ENGINEERING | REVIEW | Passed | |
| 07/29/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/29/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/29/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a detail for the construction of the water heater platform. 2.Provide metering faucets for the lavatories. The faucets shall dispense no more 0.25 gallons per cycle and the cycle shall last for at least 10-seconds. 3. The temperature mixing valves for the lavatories are to be listed to ASSE 1070. 4. Clarify the water piping isometric. 5. The fixture drain for the washer must connect to a minimum 3" horizontal drain. |
| 07/29/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/29/2019 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |