Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T19CM05348
Parcel: 12513002F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05348
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2019 SMEGGIS1 ZONING REVIEW Approved
07/29/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation of EF-1 and EF-2 so that they exhaust the restrooms whenever HVAC air is supplied to the rooms during ocupied hours.
07/29/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Coordinate exhaust fan controls with mechanical requirements. See mechanical review comments.
2. Revise the panel schedule to correlate with the water heater circuit numbers.
3. Provide for Tamper Resistant receptacles as required per NEC art 406.12.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.
07/29/2019 SMEGGIS1 ENGINEERING REVIEW Passed
07/29/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/29/2019 ROBERT SHERRY WATER REVIEW Completed
07/29/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a detail for the construction of the water heater platform.
2.Provide metering faucets for the lavatories. The faucets shall dispense no more 0.25 gallons per cycle and the cycle shall last for at least 10-seconds.
3. The temperature mixing valves for the lavatories are to be listed to ASSE 1070.
4. Clarify the water piping isometric.
5. The fixture drain for the washer must connect to a minimum 3" horizontal drain.
07/29/2019 MARTIN BROWN FIRE REVIEW Approved
07/29/2019 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed