Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05299
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. For accessibility, automatic faucets for public lavatories must operate for at least 10-seconds. At 0.5 GPM, the maximum cycle time is 30-seconds. Reference: Section 606.4, ICC/ANSI A117.1-09. 2. Verify that approved devices conforming to ASSE 1070 provide the tempered water for the public restroom lavatories. Reference: Sections 416.5 and 607.1.2, IPC 2018. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 07/29/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/30/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Keyed Note M1 on sheet M1.1 calls for the contractor to record the supply air CFM for balancing the dining area HVAC system. Calculate the required outside air for the dining area so the contractor can correctly balance the system. Reference: Section 403.3.1, IMC 2018. |
| 07/30/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/15/2019 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 08/20/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/22/2019 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 09/05/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |