Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05296
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an automatic faucet for lavatories located in public restrooms (i.e. not in a patient room), dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet will operate for at least 10-seconds for accessibility. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Verify that the specified thermostatic mixing valve, Symmons 2-225-CK-MS, is lead-free and listed to ASSE 1070; the part number appears to have been superseded by Symmons 7-225-CK-MS. Reference: Section 107.2.1, IBC 2018. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. |
| 08/15/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/15/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/19/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T19CM05296 1. Sheet G0.00; Project Description: The Level 1 Alteration references the 2018 IBC Section 602.1, and the Level 2 Alteration references the 2018 IBC Section 603.1. These references are from the 2018 IEBC. Please revise the references. 2. Sheet G0.00; Occupancy: Is the I-1 Occupancy Classification correct? Please verify. 3. Sheet G0.00; Project Data: Per the IBC Section 308.2, please indicate on the drawing whether this Institutional Group falls under Condition 1 or Condition 2. 4. Sheet G2.10; Floor Plan: The Floor Plan indicates several existing and proposed smoke compartments. The IBC Sections 407 and 408 reference smoke compartments for I-2 and I-3 Occupancy Classifications only. Please verify if this is an I-2 classification. 5. Sheet G2.10; Smoke Compartment Calculation: Per the IBC Section 407.5.1, the smoke compartment size shall not be more than 22,500 SF. Please revise the sheet note indicating 23,500 SF. 6. Sheet G2.10; Exit Access Travel Distance: Per the IBC Table 1017.2, the Exit Access Travel Distance for an I-1 Occupancy Classification is 250 feet, but 200 feet for an I-2. Please verify the Occupancy Classification. 7. Sheet G2.10; Exit Width and Distance Calculations: Please indicate on this sheet the required exit widths. 8. Sheet G2.10; Floor Plan: Please add Grid Lines to the Floor Plan to match the enlarged floor plans (Sheets AD2.10A through AD2.10D). 9. Sheet A2.10; Floor Plan: Please add grid lines to the Floor Plan to match the Enlarged Floor Plans (Sheets A2.10A through A2.10D). 10. Sheet A7.01; Detail 1: Please provide a vertical grab bar per the ICC/ANSI A117.1 Figure 604.5.1. 11. Sheet A7.10; Partition Types (1Ac): This Sheet indicates a one hour fire partition while the Partition Types Legend (Sheet G2.10) indicates a one hour fire barrier for the same Wall Type indicator. Please coordinate. 12. General: Please provide written responses to all review comments. Reviewed by Eric Newcomb Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov |
| 08/27/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2018 IECC for the interior lighting. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC |
| 08/29/2019 | DAVID RIVERA | ZONING | REVIEW | Approv-Cond | Zoning will stamp the plan set once all other review agencies have approved. |
| 09/17/2019 | MARTIN BROWN | FIRE | REVIEW | Approved |