Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T19CM05241
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2020 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T19CM05241 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. SITE PLAN: 1. Indicate the location and size of buildings, utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the utility service for verifying correct sizes and necessary upgrades. FLOOR PLANS: 1. Roof projections may not extend to a point closer than 2 feet from the property line. Provide notation for compliance with R302.1 (City of Tucson Amended) by removing the porch roof near the property line, or provide a complete wall barrier with not less than one-hour fire-resistive construction. 2. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside. Provide notation for compliance with R302.1 (City of Tucson Amended) for the altered roof overhang. The fire protected overhang may not extend closer than 24” from the property line. SECTIONS - DETAILS: 1. Provide wall type notation for all types shown on the plan on sheet A2-0, R106.1.1. 2. Provide a complete cross-section detail from foundation to roof assembly for wall Type A exterior wall, R106.1.1. Show the minimum 12” footing depth below the undisturbed ground surface (R403.1) with 12” minimum width for wood framed walls R403.1.1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. 3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update the Section on A4.0. MECHANICAL PLANS: 1. Provide a firestop system for dryer duct or relocate from the fire resistance rated wall, R302.4. 2. Provide whole-house mechanical ventilation, R303.4; N1103.6 & M1505.4. Show the ZB80 exhaust fan with an appropriate flow rate setting on the plans. A one bedroom dwelling space up to 1500 SF requires a 45 CFM continuous setting. 3. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. ELECTRICAL PLANS: 1. Show one 20 AMP branch circuit for the dishwasher/disposal; this circuit may not serve other locations, E3703.8 City of Tucson Amended. 2. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans. 3. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3. 4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16. 5. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14. 6. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. 7. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity. OUTDOOR LIGHTING CODE 1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits. If you have any questions, please contact: Ken Van Karsen (520) 791-5550 City of Tucson Residential Plan Review |
| 10/21/2020 | NMARTEL1 | ZONING | REVIEW | Reqs Change | FROM: Nicholas Martell, Planner PROJECT: T19CM05241 2872 N Cherry Avenue Convert Detached Garage to Unit TRANSMITTAL: 10/21/2020 COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. Zoning cannot approve until the DDO is approved. Previous comments related to the DDO still apply. If you have any questions regarding this transmittal, you can reach me at Nicholas.Martell@tucsonaz.gov |