Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T19CM05235
Parcel: 10820051K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05235
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the specified check valves are listed to ASSE 1022 or ASSE 1024. [Second comment: Specify the type of backflow prevention device required for each water connection. [Initial comment: Water supply connections to coffee machines and non-carbonated beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022 or ASSE 1024. Reference: Section 608.17.1.2, IPC 2018.]
10/03/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2019 QJONES1 APPROVAL SHELF Completed
10/07/2019 QJONES1 OUT TO CUSTOMER Completed
10/07/2019 QJONES1 REJECT SHELF Completed