Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05235
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/20/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/04/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The International Plumbing Code, 2018 as amended by the City of Tucson, is the controlling code for this activity, not the 2012 International Plumbing Code. [Initial comment: The International Plumbing Code, 2018 as amended by the City of Tucson, is the controlling code for this activity, not the 2018 Idaho State Plumbing Code. Reference: Section 101.2, IPC 2018.] 2. Provide a detail to show that the installation of the wall-hung water closet complies with the manufacturer's installation instructions. Reference: Section 303.2, IPC 2018. 3. The submitted faucet, Pfister model LG42-DFOB, is not a metering faucet. [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] 4. Specify the type of backflow prevention device required for each water connection. [Initial comment: Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2018.] 5. Specify the type of backflow prevention device required for each water connection. [Initial comment: Water supply connections to coffee machines and non-carbonated beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022 or ASSE 1024. Reference: Section 608.17.1.2, IPC 2018.] 6. It is not clear that this was done.[Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.1, IPC 2018.] 7. The submitted calculations assume that only the 3-compartment sink discharges to the hydromechanical grease interceptor. See Section 1003, IPC 2018, as amended by the City of Tucson for a list of plumbing fixtures that are to discharge through a grease interceptor. Note that a hydromechanical grease interceptor must have a direct connection to the building drain, vents for the interceptor, and the installation of an external flow control device. [Initial comment: Provide sizing calculations for the gravity grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.] 8. Two grease interceptors are specified: a Zurn RC-35LP and a Thermaco Big Dipper W-200-IS. The Thermaco unit does not comply with the minimum flow rate or grease capacity requirements noted in Section 1003.3, IPC 2018, as amended by the City of Tucson. [Initial comment: Clarify the hydromechanical grease interceptor that will be used - two different units are specified.] 9. The plumbing riser diagram shows that the hot water supply to the lavatory in the public restroom does not meet the requirement of Section C404.5.2.1, IECC 2018 for the maximum distance between the hot water source and the termination of the hot water supply pipe to the lavatory. 10. Clarify the 3" wall cleanout shown floating alongside the mop sink in the plumbing riser diagram. The size of cleanouts is required to match the size of the pipe they serve. Reference: Section 708.1.5, IPC 2018. 11. The weight of the specified water heater is approximately 365-pounds. Provide a design for the platform supporting the water heater and the platform's connection to the building structure. Reference: Section 301.2, IPC 2018. |
| 09/04/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The International Mechanical Code, 2018 as amended by the City of Tucson, is the controlling code for this activity, not the 2012 International Mechanical Code. Reference: Section 101.2, IPC 2018. 2. Revise the ventilation calculations to include the Zone Air Distribution Effectiveness, Ez; see Section 403.3.1.1.1.2 and equation 4-2, IMC 2018. [Initial comment: Provide ventilation calculations for this suite - the submitted ventilation calculations do not apply to this suite. Reference: Section 401.2, IMC 2018.] 3. Comment not addressed. [Initial comment: Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2, IMC 2018.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/03/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 10/03/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/03/2019 | QJONES1 | REJECT SHELF | Completed |