Permit Number: T19CM05120
Parcel: 110120970

Address:
2600 N WYATT DR

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05120
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2019 MARTIN BROWN FIRE REVIEW Approved
07/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. The City of Tucson has adopted the 2018 International Codes , amend the General Notes on sheet G0.0 to the 2018 I-Codes . IBC 107.2.1.
2. Plan sheets M9.1 and EP607 are attached to plan set but are not noted in the Index To Drawings , amend Index . IBC 107.2.1.
3. Sheets ID7.0 and ID7.1 illustrates details for section drawings details on sheet ID7.2 , sheet ID7.3 , sheet ID7.4 , and sheet ID7.5 , but these sheets ID7.2 , ID7.3 , ID7.4 , and ID7.5 are not attached to plan set . IBC 107.2.1.
07/30/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/30/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the distance from the hot water source to the hot water termination for the public lavatory (Room 1513) complies with the requirements of Section C404.5, IECC 2018.
07/30/2019 ROBERT SHERRY WATER REVIEW Completed
08/06/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/13/2019 SAMUEL ROGERS ZONING REVIEW Approved