Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T19CM05120
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/25/2019 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/26/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The City of Tucson has adopted the 2018 International Codes , amend the General Notes on sheet G0.0 to the 2018 I-Codes . IBC 107.2.1. 2. Plan sheets M9.1 and EP607 are attached to plan set but are not noted in the Index To Drawings , amend Index . IBC 107.2.1. 3. Sheets ID7.0 and ID7.1 illustrates details for section drawings details on sheet ID7.2 , sheet ID7.3 , sheet ID7.4 , and sheet ID7.5 , but these sheets ID7.2 , ID7.3 , ID7.4 , and ID7.5 are not attached to plan set . IBC 107.2.1. |
07/30/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/30/2019 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the distance from the hot water source to the hot water termination for the public lavatory (Room 1513) complies with the requirements of Section C404.5, IECC 2018. |
07/30/2019 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/06/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/13/2019 | SAMUEL ROGERS | ZONING | REVIEW | Approved |