Permit Number: T19CM05088
Parcel: 12404050A

Address:
1535 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T19CM05088
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2019 SROGERS2 ZONING REVIEW Approved
07/17/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the ductwork and air outlet configuration for the make up air unit.
2. What are the make up air requirements (and limitations) for the existing hood.
07/17/2019 RMCCOY1 ELECTRICAL-COMMERCIAL REVIEW Approved
07/17/2019 SROGERS2 ENGINEERING REVIEW Passed
07/17/2019 RMCCOY1 BUILDING-COMMERCIAL REVIEW Approved
07/17/2019 ROBERT SHERRY WATER REVIEW Completed
07/17/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Connect the mop sink, hand sinks, and all floor sinks to the grease interceptor.
2. Verify that the dishwasher can discharge to the grease interceptor.
07/17/2019 MARTIN BROWN FIRE REVIEW Approved
07/17/2019 RMCCOY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed