Permit Number: T19CM05078
Parcel: 13608032A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T19CM05078
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/22/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the natural gas service to the kitchen. The kitchen equipment schedule (P 00.02) shows 8 appliances with a total load of 885 CFH being installed; The enlarged plumbing plan (P 05.05) shows 9 appliances being installed (including two that are “not used” on the kitchen equipment schedule) with a total load of 1478 CFH; and the natural gas riser (P 06.04) has 9 appliances with a total load of 1117 CFH being installed.
04/27/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Provide full compliance with the 2018 IECC for the lighting.
Ref; 2018 IECC
05/19/2021 JPEELDA1 FIRE REVIEW Approved Plans Reviewed by Martin Brown 2019 and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2021 NGARCIA3 OUT TO CUSTOMER Approved