Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T19CM05078
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/22/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the natural gas service to the kitchen. The kitchen equipment schedule (P 00.02) shows 8 appliances with a total load of 885 CFH being installed; The enlarged plumbing plan (P 05.05) shows 9 appliances being installed (including two that are “not used” on the kitchen equipment schedule) with a total load of 1478 CFH; and the natural gas riser (P 06.04) has 9 appliances with a total load of 1117 CFH being installed. |
| 04/27/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/05/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide full compliance with the 2018 IECC for the lighting. Ref; 2018 IECC |
| 05/19/2021 | JPEELDA1 | FIRE | REVIEW | Approved | Plans Reviewed by Martin Brown 2019 and approved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/20/2021 | NGARCIA3 | OUT TO CUSTOMER | Approved |