Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T19CM05078
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2020 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T19CM05078- New Building (Commercial - Hospital) Building Plan Review (2nd Review) Northwest Medical Center 2200 S. Houghton Road - PAD 25 Zoning - Related to DP19-0164 TRANSMITTAL DATE: March 10, 2020 DUE DATE: March 20, 2020 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a review of the building plans. Prior to a more comprehensive review by zoning the DP must be reviewed and approved prior to zoning approval of the building plans. While the building plans are consistent as it relates to the zoning review purview, zoning cannot approve the building plans until the Commercial Plans reviewer(s) have approved the building plans and CDRC has reviewed and approved the DP. 2. COMMENT: Zoning will review the building plans on the next submittal to assure consistency with the DP. If any changes are necessary to the building plans due to plan review comments that affect zoning requirements the DP will have to be revised to reflect the changes. Once the DP is approved by all reviewers and the building plans are approved by the Commercial Plans reviewers zoning can approve the building plans. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans |
| 03/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 19; Sheet G02.02; Second Floor Life Safety Plan: The note above NICU Room 2612 referencing the exit access distance was not revised. Please verify. 2. Previous Comment 26; Sheet A01.31; Third Floor Plan: This sheet was not included in this submittal. Please verify. 3. Previous Comment 27; Sheet A02.12; Pharmacy Plan: The hazardous materials and their quantities were not indicated on the drawings. In addition, the maximum allowable quantities were not verified using the IBC Tables 307.1(1) and 307.1(2). The IBC Sections 307 and 414 indicate provisions in those Sections with occupancies using the storage of hazardous materials shall apply. Section 414.1.3 asks for a report that identifies the maximum expected quantities of hazardous materials to be stored, and the methods of protection for those materials. These material quantities and methods of protection shall be indicated on the construction documents. Please provide. 4. Previous Comment 28; Sheet A02.16; Floor Plan: Please see Comment 3. 5. Previous Comment 45; Sheets A03.14 and A03.15 (Curtain Walls): Sheet A03.15 was not included in this submittal. Please verify. 6. Previous Comment 51; Sheets A05.01, A05.02, and A05.03; Building Sections: None of these sheets were included in this submittal. Please verify. 7. Previous Comment 52; Sheet A07.05; Sections 5 and 6: This sheet was not included in this submittal. Please verify. 8. Previous Comment 56; Sheet ID01.00B; Finish Schedule: A reference indicating interior wall and ceiling finishes meet the IBC Table 803.13 for flame spread/smoke developed classifications was not added to this sheet. Please provide. 9. Previous Comment 57; Sheets ID02.31 and ID02.32: These sheets were not included in this submittal. Please verify. 10. Previous Comment 74; Sheets S1.04A through S1.04D: A Key Plan was not indicated on Sheet S1.04D. Please provide. 11. Previous Comment 76; Sheet S4.01; Detail 1: A note in this detail references Sheet ID02.3 for construction/control joint locations. Sheet ID02.3 was not included in this submittal. Please verify. 12. Previous Comment 81; General: A Special Inspection Certificate was not found in this submittal. Please verify. 13. General: Please verify all project sheets are included in the next submittal. 14. General: Please provide written responses to all review comments. |
| 03/16/2020 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. The intent of having two sources of domestic water for the hospital is "...to minimize the potential for an interruption of the supply of water in the event of a water main or water service pipe failure." You have a single source of failure at the 6" water valve that serves the hospital. [Initial comment: The site utility drawing, C 06.03, shows a single water supply to the proposed hospital. Provide two water service pipes to the hospital per Section 609.2, IPC 2018.] 2. Comment not resolved. What is the total water demand for the hospital in gallon per minute? [Initial comment: What is the total water demand for the hospital? Reference: Section 107.2.1, IBC 2018.] |
| 03/19/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. As per the previous plan review comments, the responses and or plan changes may still require additional information or clarification to verify code compliance for the installations. 2. Previous review comments; #4(a). Perhaps the review comment was not stated clear enough to understand the reviewer's intent. Some of the feeders for the panels and other equipment shown in the line diagrams E00.03 and E00.04 have a number in the hexagon box that correlate with the feeder schedule. Please provide this for all the feeders shown. #4(b). Indicate on the plan what is being used as the grounding electrodes for transformers. #4(c). Identify the transformers on the line diagrams as previously requested. #4(g). Ref; Plan Sheet E06.00, Detail #7. Note#3 is still unacceptable for branch circuit assignment. The response stated." POWER CONNECTIONS HAVE BEEN ADDED". Where? #4(h). Please indicate what plan sheet shows the elevator feeders, panel designations. 3. As requested per the previous plan review comment #5. The Elevators are still not shown on the equipment schedules or line diagrams. The response states,"ELEVATOR POWER CONNECTIONS HAVE BEEN ADDED TO DRAWINGS SET". Where? 4. Previous comment #6(b) Plan Sheets E01.22 and E01.23 are missing in this 2nd plan set. …In your response, please identify the specific plan in question. 5. Previous comment #6(e). Response," REFER TO LIGHTING LEGEND ON SHEET E00.00". This plan sheet was not included in this 2nd plan set. 6. Previous comment #11. Response," OPERATING ROOMS COMPLY WITH 8 DUPLEX RECEPTICLES BEING PROVIDED IN THE EQUIPMENT BOOM". Identify the equipment boom(s) and location on the plan. See NEC art 517.19c and provide quantity and location of the receptacles including branch circuits assigned per 517.19c. 7. Ref; Plan Sheet E07.00. Panel schedule 'PEH1' is overlapping into the panel below it. Provide proper spacing. 8. Please be advised. Due to the nature of the plan review comments and responses, additional comments may be generated at the subsequent review due to insufficient information provided. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 03/23/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide labels for the riser diagrams on sheet P06.00. Where are the riser diagrams for the main water lines and drain lines? Remove artifacts floating on the drawings. [Initial comment: Provide water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2018]. 2. Lavatory model L-1 installed in public restrooms requires a metering faucet. Provide a statement requiring that the time out for the automatic faucets be set to 30-seconds. [Initial comment: Provide automatic faucets for lavatories located in public restrooms (including staff restrooms). Verify that the automatic faucets will operate for a minimum time of 10-seconds but have an automatic time out to limit the amount of water dispensed to 0.25 gallons per cycle. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] 3. The enlarged plumbing drawings for the restrooms and the unfinished riser diagram only show the DHW supply passing by the lavatories but do not note a maximum distance from the hot water source. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories (including staff restrooms) complies with the requirements of Section C404.5, IECC 2018. 4. The revised plumbing fixture schedule does not show DHW connected to the clinical sink. [Initial comment: Revise the plumbing fixture schedule to include hot water for the clinical sink (CS-1). Reference: Section 607.1, IPC 2018.] 5. The backwater valve was not located on the revised drawings but the building drain for the boiler room also is connected to horizontal drains serving the second floor. Drains serving floors that are more than 12" above the rim of the next upstream manhole may not pass through a backwater valve. [Initial comment: The FFE for the Boiler Room (1983) is less than 12" above the rim elevation of manhole MH-4. Provide a backwater valve for the building drain from the Boiler Room. Reference: Section 714.1, IPC 2018 as amended by the City of Tucson.] 6. The storm water piping schedules in the 2018 IPC are based on the storm water flow rate in GP. Convert the roof areas and the adjacent vertical wall areas into the flow rate by multiplying the area by 0.031 GPM/square foot. Provide the slope of the horizontal storm water pipe and finish labeling the pipe sizes on the riser diagrams. [Initial comment: Provide roof drainage and hydraulic scupper size calculations based on the 100-year hourly rainfall rate for Tucson, 3" per hour. Reference: Sections 1101.7, 1106, and 1108, IPC 2018.] 7. The State of Arizona requires a flow rate of 50 GPM per elevator shaft. No sump pumps are scheduled so the discharge of the pumps in unknown. The two sump pump discharge pipes located south of elevators 2 and 3 discharge to a 6" pipe that doesn't appear to connect to anything. The sump pump discharge pipe north of elevator 5 connects to a 4" building drain; the available capacity of the 4" building drain is not known. [Initial comment: Show the location of the elevator sump pumps, the route and size of their discharge piping, and their termination points. Reference: Section 107.2.1, IBC 2018.] 8. Finnish labeling the pipe sizes and loads for each outlet on the natural gas riser diagram [Initial comment: Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 402.2, IFGC 2018.] 9. Clarify the waste and vent piping shown on sheet P02.11 between columns 6 and 7, A.2 and B; it appears to be outside of the building. |
| 03/24/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/26/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. COMcheck envelope compliance not found in initial submittal. [Initial comment: Demonstrate energy code compliance for the building envelope and the mechanical systems using calculations based on the current code. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018.] 2. Deferred submittals must be identified on the construction documents by the architect and approved by the building official as part of the approval process. [Initial comment: Provide structural calculations and details to show how the Computer Room AC units are to be connected to the building structure. Reference: Section 302.1, IMC 2018.] 3. Hood installation is not allowed to be a deferred submittal. [Initial comment: Provide structural calculations and details to show that the Type I hoods are supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018.] 4. Field-applied grease duct enclosures are not applicable to hazardous exhaust ducts. Sections 510.7.2 and 510.7.3, IMC 2018 explicitly state that fire-rated shafts are required for the penetration of floor/ceiling assemblies and fire-rated wall assemblies. [Initial comment: The hazardous exhaust duct to EF4-5 penetrates both a floor/ceiling assembly and a fire-resistance rated partition. Provide an enclosing fire-resistance rated shaft for the duct. Reference: Section 510.7.2 and 510.7.3, IMC 2018.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/25/2020 | KROBLES1 | OUT TO CUSTOMER | Completed |