Permit Number: T19CM05074
Parcel: 116150340

Address:
305 N BOULDER TE

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T19CM05074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2020 SAMUEL ROGERS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Samuel Rogers
Planner - PDSD

PROJECT:
T19CM0574
305 N Boulder TE
New SFR

TRANSMITTAL: 1/10/20
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The maximum wall height on the southeast (left) elevation is 19'-8" requiring a setback of 12'-10". The proposed southeast setback is 10'. The maximum height on the northwest (right) elevation is 16'-9" requiring a setback of 11'-1". The proposed northwest setback is 8'.
05/11/2020 ARUIZ1 BUILDING-RESIDENTIAL REVIEW Reqs Change